Structure: 
	
		
			| Frame | Filter Media | Seperator | Flange | 
	
	
		
			| Aluminum/Galvanised steel | Meltblow PP/Glassfiber | Stiff corrugated cardboard | With header/no header | 
	
Product Features:
- Large airflow
- Low pressure drop
- Firm contruction
Application
Secondary filtration in central ventilation systems, particularly to protect and extend the life of HEPA/ULPA filters. They are suitable for use in ventilation and air conditioning systems of various airflows.            
 
            
                General technical data:
- F5~F8 EN779; MERV9~14 ASHRAE
- Final pressure drop: 2~3 times initial pressure drop
- DIN 53438 Flammability: F1
- UL 900 Standard: Class 2
- Thermal Stability:80celcius(High temperature resistant types available)
- Humidity: 100% RH
Sample data: 
	
		
			| W*H*D(mm) | Filter Class | Filter Area(m2) | Airflow(CMH) | Intial Pressure Drop(Pa) | 
	
	
		
			| 593*593*150 | F5 | 2.53 | 2520 | 70 | 
		
			| F6 | 80 | 
		
			| F7 | 95 | 
		
			| F8 | 110 | 
		
			| 287*593*150 | F5 | 1.27 | 1230 | 70 | 
		
			| F6 | 80 | 
		
			| F7 | 95 | 
		
			| F8 | 110 | 
		
			| 592*592*292 | F5 | 5.51 | 3400 | 70 | 
		
			| F6 | 80 | 
		
			| F7 | 95 | 
		
			| F8 | 110 | 
		
			| 287*592*292 | F5 | 2.73 | 1650 | 70 | 
		
			| F6 | 80 | 
		
			| F7 | 95 | 
		
			| F8 | 110 | 
	
             
            
                https://drive.google.com/file/d/0Bxk0k7JxzX13VENHN2E3dDRURXc/view